Thermoelectric Cooling by the Numbers
Seebeck and Peltier effects, module datasheets, operating points, heat sinks, cabinet loads, condensation, control and reliability
How thermoelectric coolers pump heat with no moving parts, and how to size, sink, power, control and judge one for a sealed cabinet or small chiller, worked with numbers.
Start readingAbout this book
Pass a direct current through a junction of two different conductors and the junction warms or cools, depending on the direction of the current. Build the junction from two well-chosen semiconductors, repeat it a hundred times between two ceramic plates, and the result is a thermoelectric cooler: a flat, silent, solid-state heat pump a few millimetres thick that moves heat from one face to the other at the rate the current sets, and reverses when the current does. It has no compressor, no refrigerant and no moving parts apart from the fans on its heat exchangers.
It also has a low coefficient of performance, a hard limit on the temperature difference it can make, and a hot side that must reject both the heat pumped and all the electrical power supplied. Thermoelectric coolers are excellent for small, sealed, quiet or precise jobs and poor for large ones. This book shows how to tell which a job is and how to design for it with numbers: the physics of the effects and the materials, the module’s datasheet and the model behind it, the operating point, the heat sinks, the heat load, condensation, power and control, reliability, and the choice between thermoelectric, compressor and ventilation cooling.
It is for mechanical, electrical, controls and product engineers, maintenance planners and buyers. It assumes engineering training and comfort with basic heat transfer and electricity; the solid-state physics is explained from the start as it is used. Each chapter works the running case with real numbers, includes a plausible mistake and how it was found, links the BIZOMAT tools that do the chapter’s calculations, and ends with an exercise and its worked answer.
The running case
Every chapter follows one installation. This is an illustration. An irrigation trust in the Riverland of South Australia runs a pump station near Loxton whose control and telemetry equipment sits in a sealed outdoor cabinet, TC-1, on the shaded south wall of the pump shed:
- The cabinet: powder-coated steel, 600 mm high, 500 mm wide and 250 mm deep, sealed to IP66 against dust and hosing. It holds the station’s controller, a 4G router, a radio, a 24 V power supply, I/O, a battery charger and a 12 V standby battery, giving off 45 W in all.
- The problem: design summer air temperatures reach 45 °C, and the router and battery maker want the cabinet’s air kept at or below 35 °C. Fans and filters cannot cool a cabinet below the outside air, and filters clog with Riverland dust.
- The cooler: a thermoelectric air-to-air cooler, CC-1, with three modules on a 24 V supply, a finned hot-side heat sink and fan outside the cabinet and a finned cold-side exchanger and fan inside.
- A second job: the station’s water-quality autosampler has a small insulated sample box, SC-1, that must hold its samples at 4 °C, cooled by a single module.
The modules are a generic 127-couple bismuth telluride type rated 6.0 A, 15.4 V and a maximum temperature difference of 68 K at a 27 °C hot side. Dimensions, loads, temperatures, prices and results are the trust’s working figures or are calculated from stated assumptions. They do not describe BIZOMAT work or any real trust, manufacturer, supplier or customer. Prices are in Australian dollars, including GST where stated.
How to use the book
Read Chapters 1 to 4 in order: they build the physics and the module model that the rest uses. Chapters 5 and 6 go together on the heat sinks and the heat load, and Chapter 7 on condensation follows from them. Chapters 8 and 9 can be read in either order, and Chapter 10 brings the choice of cooling method and its cost together.
Every calculation in the book was checked by running it, and the BIZOMAT tools linked from each chapter were checked against the calculations they perform. Where a tool was built for a different purpose but answers one question in a chapter, such as the enclosure cooling tool’s refusal to cool below ambient, the chapter says what is used and what is not.
Source limits and professional responsibility
This book is educational. Electrical installations, enclosures for hazardous areas, medical and food refrigeration, and equipment carrying safety functions are governed by standards, regulations and certification requirements that this book does not cover. Module, heat sink and fan ratings must be taken from the maker’s current data, and designs for real equipment must be checked by testing and by competent people responsible for them.
Who this book is for
Mechanical, electrical, controls and product engineers, maintenance planners and buyers who specify, design, test or replace thermoelectric coolers for sealed cabinets, instruments, sample chillers and electronics.
What you will learn
- Explain the Seebeck, Peltier and Thomson effects, why semiconductors pump heat and metals do not, and what the figure of merit ZT limits.
- Derive a module's Seebeck coefficient, resistance and conductance from its datasheet and calculate the heat pumped, power and COP at any current and temperatures.
- Size the modules, hot-side heat sink and cold-side exchanger together for a cabinet's heat load, including walls, insulation and sun.
- Check the cold side for condensation, and choose a supply, connection and control scheme that keeps the COP and the modules' life.
- Judge reliability, running cost and the choice between thermoelectric, compressor and plain ventilation cooling with numbers.
Inside this book
Chapters
- 01Three thermoelectric effectsHow electrons carry heat as well as charge, the Seebeck voltage, Peltier heat at a junction and the Thomson effect, how they are related, and the heat balance at a cooler's cold junction.
- 02Materials and the figure of meritWhy a good thermoelectric needs a large Seebeck coefficient, high electrical and low thermal conductivity, the Wiedemann–Franz limit on metals, ZT, and the limits on ΔT and COP.
- 03Reading a module datasheetWhat Imax, Vmax, ΔTmax and Qmax mean, how to derive a module's Seebeck coefficient, resistance and conductance from them, and how to predict heat pumped, voltage, power and COP at any operating point.
- 04Choosing the operating pointHow heat pumped, power and COP change with current, the current for best COP and for most cooling, how many modules to use, and why the cheapest choice on paper can let a cabinet overheat.
- 05Heat sinks and the system balanceThe thermal circuit from outside air to cabinet air, how the exchangers add to the modules’ temperature difference, solving the balance, and why a dusty heat sink can cost a quarter of the cooling.
- 06The cabinet heat loadInternal heat, heat through the walls, sol-air temperature for sun on the cabinet, what insulation gains and costs, why fans cannot cool below ambient, and a load estimate that left out the walls.
- 07Condensation and the cold sideWhy a cooler’s cold side can sweat inside a sealed cabinet, dew point and humidity ratio, how the setpoint sets the margin, managing condensate and protecting modules from moisture.
- 08Power supplies and controlWiring modules in series or parallel, the switch-on surge, why ripple and unfiltered PWM waste cooling, on–off and proportional control, interlocks, and reversing current to heat or defrost.
- 09Reliability and lifeHow thermoelectric coolers wear out, Weibull and series-system reliability for a cooler, field MTBF with confidence bounds, spares, and a thermostat that cycled a module to death.
- 10Thermoelectric, compressor or ventilationComparing thermoelectric, compressor and ventilation cooling for a sealed cabinet on COP, annual energy, running cost, sealing, maintenance and failure, with a year worked band by band.
Apply This in Practice
Use these BIZOMAT tools to try the method from this reading with your own numbers.
Explained in this book
Enclosure Cooling Airflow (Heat Load, Wall Losses, Fan Airflow Needed)
Sizes fan ventilation from the internal heat and wall losses and refuses when the cabinet limit is below the outside air, which shows why a sealed cabinet at 45 °C needs a refrigerating cooler.
Used in The cabinet heat load
Applies this method
Heat Engine Carnot Limit Check (Ideal Efficiency, Second-Law Efficiency, Most Work, Least Heat Rejected)
Checks a thermoelectric generator's stated efficiency against the Carnot limit between its hot and cold sides; the chapter confirms a 3.5% figure for a module on a 120 °C pipe as credible.
Applies this method
Heat Pump and Chiller COP Check (Carnot Limit, Second-Law Efficiency, Running Cost)
Compares the thermoelectric and compressor coolers' COP with the Carnot limit at their face or refrigerant temperatures, giving second-law efficiencies of about 9% and 20% on the design day.
Applies this method
Moist Air Dew Point and Surface Condensation Check (Humidity Ratio, Enthalpy, Dew-Point Margin)
Gives the cabinet air's dew point and humidity ratio and checks the cold-side fins against it with a margin, showing why a 25 °C setpoint made the cooler sweat and 32 °C kept it dry.
Used in Condensation and the cold side
Applies this method
MTBF Confidence Bounds (Field or Test Failures, Chi-Square Limits, Requirement Check)
Gives the fleet's MTBF from cooler-hours and failures with chi-square confidence bounds, showing that three failures in 490,560 hours do not yet demonstrate a 100,000 h target.
Used in Reliability and life
Applies this method
System Reliability from Weibull Components (Series and Redundancy)
Combines the cooler's fans, module string and controller as Weibull blocks in series to give its five-year reliability and weakest block, the basis for the fan replacement interval.
Used in Reliability and life
Applies this method
Thermoelectric Cooler Check (TEC Module Constants from the Datasheet, Heat Pumped, Power, COP, Hot-Side Heat)
Derives a module's Seebeck coefficient, resistance and conductance from Imax, Vmax and ΔTmax, then gives heat pumped, voltage, power, COP and hot-side heat at the cabinet cooler's operating point.
Used in Reading a module datasheet
Applies this method
Weibull Reliability and B10 Life
Turns a fan's L10 life and wear-out shape into its reliability, B10 life and mean life over five years of continuous running in the cabinet cooler.
Used in Reliability and life
Related Tools and Examples
Useful alongside
Critical Spares Plan (Poisson Failures over the Lead Time, Spares for a Service Level)
Sets the number of spare coolers for a fleet from the MTBF and workshop turnaround with a Poisson model; the chapter notes that fans wear out, so the random-failure model needs care.
Related to Reliability and life
References and source notes
The manuscript and worked examples are original BIZOMAT writing. References inform particular concepts; their authors do not endorse this book. Web references were consulted on 3 November 2026.
- Y. M. Galperin, lecture notes for course FYS 448, Department of Physics, University of Oslo. Introduction to Modern Solid State Physics (2001). Copyright work, used only as a map of ideas: transport of charge and heat by electrons, the thermoelectric (Seebeck) and Peltier coefficients and their relation, the Wiedemann–Franz law, and the lattice's share of heat conduction. No text, equations as set out there, figures or problems are reproduced, and all cases and calculations are BIZOMAT originals.
- H. J. Goldsmid, Springer. Introduction to Thermoelectricity (2016). Second edition (Springer Series in Materials Science 121). Background for the thermoelectric effects, the figure of merit, bismuth telluride materials, module theory, optimum current and coefficient of performance used in Chapters 1 to 4.
- D. M. Rowe (editor), CRC Press. CRC Handbook of Thermoelectrics (1995). Background for module construction, performance modelling from datasheet parameters, heat exchangers for modules and reliability considerations used in Chapters 3, 5 and 9.
- International Electrotechnical Commission. IEC 60529, Degrees of protection provided by enclosures (IP Code) (2013). Named by number and scope only, for the IP ratings of the sealed cabinet in the running case. Its requirements are not reproduced.
- National Institute of Standards and Technology. NIST/SEMATECH e-Handbook of Statistical Methods (2012). Background for the Weibull, exponential and confidence-bound methods used in Chapter 9 and in the BIZOMAT tools linked from it.