BIZOMAT MAKEOS · Hydraulics

Heat Exchanger LMTD and Area

What log mean temperature difference and area does this heat exchanger need for the duty?

Log mean temperature difference for counter-flow or parallel-flow exchange, the area needed for a heat duty at an overall coefficient, and a temperature-cross check.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
Hot fluid in°CInlet temperature of the hot fluid.
Hot fluid out°COutlet temperature of the hot fluid.
Cold fluid in°CInlet temperature of the cold fluid.
Cold fluid out°COutlet temperature of the cold fluid.
Flow arrangementchoiceFlow arrangement (shell-and-tube with several passes needs a correction factor, not included).
Heat dutykWHeat to transfer.
Overall heat transfer coefficientW/(m²·K)Overall coefficient for the exchanger type and fluids (oil to water about 200–600 W/m²K).

What each input means

Open an input to see what it is, its units, the worked example and the common mistakes, with a small diagram.

What this means: Hot fluid in
Illustration: Hot fluid inA thermometer whose level rises with Hot fluid in; the level follows the value you type.Th,inExample: 70 °CHot fluid in
What it is
The temperature of the hot fluid as it enters the heat exchanger.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -100 °C to 1000 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 70 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Get it right
Enter degrees Celsius; only the differences matter in the result.
What this means: Hot fluid out
Illustration: Hot fluid outA thermometer whose level rises with Hot fluid out; the level follows the value you type.Th,oExample: 50 °CHot fluid out
What it is
The temperature of the hot fluid as it leaves the heat exchanger, after giving up heat.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -100 °C to 1000 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 50 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Get it right
It must be lower than the hot inlet temperature.
What this means: Cold fluid in
Illustration: Cold fluid inA thermometer whose level rises with Cold fluid in; the level follows the value you type.Tc,inExample: 25 °CCold fluid in
What it is
The temperature of the cold fluid as it enters the heat exchanger.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -100 °C to 1000 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 25 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
What this means: Cold fluid out
Illustration: Cold fluid outA thermometer whose level rises with Cold fluid out; the level follows the value you type.Tc,oExample: 35 °CCold fluid out
What it is
The temperature of the cold fluid as it leaves the heat exchanger, after picking up heat.
Units and format
Enter a number in °C: degrees Celsius. The form accepts -100 °C to 1000 °C. Required: the tool does not calculate until every input is valid.
Example
The form opens with 35 °C as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Get it right
In parallel flow the cold outlet cannot exceed the hot outlet; the tool rejects temperatures that cross.
What this means: Flow arrangement
Illustration: Flow arrangementThe options for Flow arrangement, with the one currently selected highlighted.Counter-flowParallel flowExample: Counter-flowFlow arrangement
What it is
Whether the two fluids flow in opposite directions (counter-flow) or the same direction (parallel flow) through the exchanger.
Units and format
Choose one of 2 options from the list: Counter-flow; Parallel flow.
Example
The form opens with “Counter-flow” selected as a worked example. Choose the option that matches your case.
Get it right
Multi-pass shell-and-tube exchangers need a correction factor that this tool does not apply.
What this means: Heat duty
Illustration: Heat dutyA motor driving a shaft; Heat duty is the rate at which it does work, energy per second.QExample: 20 kWHeat duty
What it is
The heat that must pass from the hot fluid to the cold fluid.
Units and format
Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 1000000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 20 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
The area required rises in direct proportion to the duty.
Get it right
It should match the heat given up by the hot fluid and gained by the cold one.
What this means: Overall heat transfer coefficient
Illustration: Overall heat transfer coefficientHeat flowing from a hot side to a cold side through a wall or into a material; Overall heat transfer coefficient sets how much heat moves or is stored.hotcoldUExample: 400 W/(m²·K)Overall heat transfer coefficient
What it is
The overall heat transfer coefficient for the exchanger type and fluids, including wall and fouling resistances, from the exchanger maker or a heat transfer reference.
Units and format
Enter a number in W/(m²·K): watts per square metre per kelvin. The form accepts 0.000001 W/(m²·K) to 100000 W/(m²·K). Required: the tool does not calculate until every input is valid.
Example
The form opens with 400 W/(m²·K) as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
The area required falls in inverse proportion.
Get it right
Include fouling in this value; a clean coefficient overstates performance once in service.

Method and formulas

  1. Counter-flow: ΔT₁ = Th,in − Tc,out; ΔT₂ = Th,out − Tc,in. Parallel: ΔT₁ = Th,in − Tc,in; ΔT₂ = Th,out − Tc,out.
  2. LMTD = (ΔT₁ − ΔT₂) ÷ ln(ΔT₁ ÷ ΔT₂).
  3. Area = Q ÷ (U × LMTD).
  4. Example: the default temperatures give LMTD = 29.72 K and need 1.6824 m² for 20 kW.

Limitations

  • Pure counter-flow or parallel flow; multi-pass exchangers need the F correction factor.
  • Fouling must be included in U.
  • Example values are illustrations. Replace them with values for your actual task.

Typical uses

  • Size an oil cooler or plate heat exchanger
  • Check an existing exchanger for a new duty
  • Compare counter-flow and parallel flow

Who it is for

  • Process engineers
  • Maintenance engineers
  • Design engineers

What you get

  • Terminal temperature differences
  • LMTD
  • Area required

Interpreting the result

  • Counter-flow needs less area and allows the cold outlet to exceed the hot outlet.

References

  • Machinery’s Handbook, 29th edition (Industrial Press, 2012), printed pp. 371–378. Topic reference; no source tables or recommended settings are reproduced.

Learn the Concepts Behind This Tool

These BIZOMAT Library readings explain the method this tool uses, with worked examples.

  • Method explained here · BIZOMAT original book

    Water in the flue gas and condensing heat recovery

    In Combustion by the Numbers

    What it covers: How much water burning gas makes, the flue gas dew point and how excess air moves it, recovering latent heat with a condensing exchanger, and a flue that was never meant to be wet.

  • Method explained here · BIZOMAT original book

    Heat Transfer by the Numbers

    What it covers: Calculate heat flows in plant: energy and power, conduction through walls and pipe insulation, convection, radiation, economic insulation, heat exchangers and heating and cooling times.

BIZOMAT tools are screening and decision-support utilities. Verify important financial, engineering, safety, legal or operational decisions using appropriate professional standards and your organisation’s approved data.

Open the Heat Exchanger LMTD and Area calculator