Pump and Fan Affinity Laws
What flow, head and power will this centrifugal pump or fan give at a new speed or impeller size?
Flow, head (pressure) and power of a centrifugal pump or fan at a new speed or trimmed impeller diameter by the affinity laws, with the power saving.
Open the calculatorRuns in your browser. No account needed.
How this tool works
Inputs, units and where to find them
| Input | Unit | Typical source |
|---|---|---|
| Present flow | m³/h | Flow at the present operating point, from the pump curve or a flow meter. |
| Present head | m | Head (or fan pressure) at that point. |
| Present shaft power | kW | Shaft power at that point, from the curve or measured input × motor efficiency. |
| Present speed | rpm | Present speed. |
| New speed | rpm | New speed (e.g. with a VSD or new pulleys). |
| Present impeller diameter | mm | Present impeller diameter. |
| New impeller diameter | mm | New (trimmed) impeller diameter; equal to the present one for speed changes only. |
What each input means
Open an input to see what it is, its units, the worked example and the common mistakes, with a small diagram.
What this means: Present flow
- What it is
- The flow the pump or fan delivers now at the present speed and impeller size, from its curve at the operating point or a flow meter.
- Units and format
- Enter a number in m³/h: cubic metres per hour. The form accepts 0.000001 m³/h to 10000000 m³/h. Required: the tool does not calculate until every input is valid.
- Example
- The form opens with 60 m³/h as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
- Effect on the result
- New flow scales in direct proportion.
- Get it right
- Use a real operating point, not the pump’s best-efficiency rating unless it runs there.
What this means: Present head
- What it is
- The head the pump develops now at the present operating point, or the pressure for a fan, from the pump curve or measured pressures.
- Units and format
- Enter a number in m: metres. The form accepts 0.000001 m to 100000 m. Required: the tool does not calculate until every input is valid.
- Example
- The form opens with 30 m as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
- Effect on the result
- New head scales in direct proportion.
- Get it right
- The affinity laws assume no static head; with a large static lift the real new point differs.
What this means: Present shaft power
- What it is
- The power going into the pump or fan shaft now at the present operating point, from the pump curve or measured motor input times motor efficiency.
- Units and format
- Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 1000000 kW. Required: the tool does not calculate until every input is valid.
- Example
- The form opens with 7 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
- Effect on the result
- New power scales in direct proportion.
- Get it right
- Use shaft power, not electrical input, unless you accept that motor losses are ignored.
What this means: Present speed
- What it is
- The speed the pump or fan shaft runs at now, from the motor nameplate, drive display or a tachometer.
- Units and format
- Enter a number in rpm: revolutions per minute. The form accepts 0.000001 rpm to 100000 rpm. Required: the tool does not calculate until every input is valid.
- Example
- The form opens with 2900 rpm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
- Effect on the result
- A higher present speed for the same new speed means a larger reduction.
- Get it right
- Use the actual running speed under load, not the synchronous speed of the motor.
What this means: New speed
- What it is
- The speed you plan to run at, for example with a variable speed drive or different pulleys.
- Units and format
- Enter a number in rpm: revolutions per minute. The form accepts 0.000001 rpm to 100000 rpm. Required: the tool does not calculate until every input is valid.
- Example
- The form opens with 2400 rpm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
- Effect on the result
- Flow scales with speed, head with its square and power with its cube.
- Get it right
- Set it equal to the present speed when only trimming the impeller.
What this means: Present impeller diameter
- What it is
- The diameter of the impeller fitted now, from the pump data sheet or by measuring.
- Units and format
- Enter a number in mm: millimetres. The form accepts 0.000001 mm to 100000 mm. Required: the tool does not calculate until every input is valid.
- Example
- The form opens with 200 mm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
- Get it right
- For speed changes only, enter the same value as the new diameter.
What this means: New impeller diameter
- What it is
- The diameter of the impeller after trimming, or the same as the present diameter if only the speed changes.
- Units and format
- Enter a number in mm: millimetres. The form accepts 0.000001 mm to 100000 mm. Required: the tool does not calculate until every input is valid.
- Example
- The form opens with 200 mm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
- Effect on the result
- Flow scales with diameter, head with its square and power with its cube.
- Get it right
- Large trims make the affinity laws inaccurate; the tool warns when that happens.
Method and formulas
- Q₂ = Q₁ (n₂/n₁)(D₂/D₁).
- H₂ = H₁ (n₂/n₁)²(D₂/D₁)².
- P₂ = P₁ (n₂/n₁)³(D₂/D₁)³.
- Example: slowing from 2900 to 2400 rpm cuts power from 7 to 3.9677 kW.
Limitations
- Applies along a system curve with no static head; with static head, the operating point and savings are smaller.
- Impeller trimming beyond about 10–20% departs from the laws and lowers efficiency.
- Example values are illustrations. Replace them with values for your actual task.
Typical uses
- Estimate savings from a variable speed drive
- Predict the effect of trimming an impeller
- Re-rate a fan at a new pulley ratio
Who it is for
- Hydraulic and process engineers
- Maintenance engineers
- Design engineers
What you get
- New flow, head and power
- Power saving
Interpreting the result
- Plot the new pump curve against the system curve to find the real operating point.
References
- Machinery’s Handbook, 29th edition (Industrial Press, 2012), printed pp. 3024–3027. Topic reference; no source tables or recommended settings are reproduced.
Learn the Concepts Behind This Tool
These BIZOMAT Library readings explain the method this tool uses, with worked examples.
Method explained here · BIZOMAT original book
Pumps, fans and similarity: affinity laws and specific speed
In Scale Models by the Numbers
What it covers: Derive the affinity laws from dimensionless groups, apply them to a variable-speed pump and a ventilation fan, classify machines by specific speed, and see why model pump efficiency is stepped up.
Method explained here · BIZOMAT original book
Fans, pumps and energy savings
In Variable-Speed Drives by the Numbers
What it covers: How the fan and affinity laws predict the power saved by slowing a fan or pump, why static head cuts the saving, how to measure the before and after, and how to appraise a drive as an investment.
BIZOMAT tools are screening and decision-support utilities. Verify important financial, engineering, safety, legal or operational decisions using appropriate professional standards and your organisation’s approved data.