BIZOMAT MAKEOS · Hydraulics

Pump and Fan Affinity Laws

What flow, head and power will this centrifugal pump or fan give at a new speed or impeller size?

Flow, head (pressure) and power of a centrifugal pump or fan at a new speed or trimmed impeller diameter by the affinity laws, with the power saving.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
Present flowm³/hFlow at the present operating point, from the pump curve or a flow meter.
Present headmHead (or fan pressure) at that point.
Present shaft powerkWShaft power at that point, from the curve or measured input × motor efficiency.
Present speedrpmPresent speed.
New speedrpmNew speed (e.g. with a VSD or new pulleys).
Present impeller diametermmPresent impeller diameter.
New impeller diametermmNew (trimmed) impeller diameter; equal to the present one for speed changes only.

What each input means

Open an input to see what it is, its units, the worked example and the common mistakes, with a small diagram.

What this means: Present flow
Illustration: Present flowA pipe with liquid or gas moving through it; Present flow is the volume that passes per unit of time.Q₁Example: 60 m³/hPresent flow
What it is
The flow the pump or fan delivers now at the present speed and impeller size, from its curve at the operating point or a flow meter.
Units and format
Enter a number in m³/h: cubic metres per hour. The form accepts 0.000001 m³/h to 10000000 m³/h. Required: the tool does not calculate until every input is valid.
Example
The form opens with 60 m³/h as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
New flow scales in direct proportion.
Get it right
Use a real operating point, not the pump’s best-efficiency rating unless it runs there.
What this means: Present head
Illustration: Present headA block with a vertical dimension line from its base to its top, marking the height Present head.H₁Example: 30 mPresent head
What it is
The head the pump develops now at the present operating point, or the pressure for a fan, from the pump curve or measured pressures.
Units and format
Enter a number in m: metres. The form accepts 0.000001 m to 100000 m. Required: the tool does not calculate until every input is valid.
Example
The form opens with 30 m as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
New head scales in direct proportion.
Get it right
The affinity laws assume no static head; with a large static lift the real new point differs.
What this means: Present shaft power
Illustration: Present shaft powerA motor driving a shaft; Present shaft power is the rate at which it does work, energy per second.P₁Example: 7 kWPresent shaft power
What it is
The power going into the pump or fan shaft now at the present operating point, from the pump curve or measured motor input times motor efficiency.
Units and format
Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 1000000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 7 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
New power scales in direct proportion.
Get it right
Use shaft power, not electrical input, unless you accept that motor losses are ignored.
What this means: Present speed
Illustration: Present speedA turning disc with a marker; Present speed is how many full turns it makes in each minute.turns of the shaftper minuten₁Example: 2900 rpmPresent speed
What it is
The speed the pump or fan shaft runs at now, from the motor nameplate, drive display or a tachometer.
Units and format
Enter a number in rpm: revolutions per minute. The form accepts 0.000001 rpm to 100000 rpm. Required: the tool does not calculate until every input is valid.
Example
The form opens with 2900 rpm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A higher present speed for the same new speed means a larger reduction.
Get it right
Use the actual running speed under load, not the synchronous speed of the motor.
What this means: New speed
Illustration: New speedA turning disc with a marker; New speed is how many full turns it makes in each minute.turns of the shaftper minuten₂Example: 2400 rpmNew speed
What it is
The speed you plan to run at, for example with a variable speed drive or different pulleys.
Units and format
Enter a number in rpm: revolutions per minute. The form accepts 0.000001 rpm to 100000 rpm. Required: the tool does not calculate until every input is valid.
Example
The form opens with 2400 rpm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Flow scales with speed, head with its square and power with its cube.
Get it right
Set it equal to the present speed when only trimming the impeller.
What this means: Present impeller diameter
Illustration: Present impeller diameterA circle with a line straight through its centre from edge to edge, marking the diameter Present impeller diameter.D₁measured acrossthe centreExample: 200 mmPresent impeller diameter
What it is
The diameter of the impeller fitted now, from the pump data sheet or by measuring.
Units and format
Enter a number in mm: millimetres. The form accepts 0.000001 mm to 100000 mm. Required: the tool does not calculate until every input is valid.
Example
The form opens with 200 mm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Get it right
For speed changes only, enter the same value as the new diameter.
What this means: New impeller diameter
Illustration: New impeller diameterA circle with a line straight through its centre from edge to edge, marking the diameter New impeller diameter.D₂measured acrossthe centreExample: 200 mmNew impeller diameter
What it is
The diameter of the impeller after trimming, or the same as the present diameter if only the speed changes.
Units and format
Enter a number in mm: millimetres. The form accepts 0.000001 mm to 100000 mm. Required: the tool does not calculate until every input is valid.
Example
The form opens with 200 mm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Flow scales with diameter, head with its square and power with its cube.
Get it right
Large trims make the affinity laws inaccurate; the tool warns when that happens.

Method and formulas

  1. Q₂ = Q₁ (n₂/n₁)(D₂/D₁).
  2. H₂ = H₁ (n₂/n₁)²(D₂/D₁)².
  3. P₂ = P₁ (n₂/n₁)³(D₂/D₁)³.
  4. Example: slowing from 2900 to 2400 rpm cuts power from 7 to 3.9677 kW.

Limitations

  • Applies along a system curve with no static head; with static head, the operating point and savings are smaller.
  • Impeller trimming beyond about 10–20% departs from the laws and lowers efficiency.
  • Example values are illustrations. Replace them with values for your actual task.

Typical uses

  • Estimate savings from a variable speed drive
  • Predict the effect of trimming an impeller
  • Re-rate a fan at a new pulley ratio

Who it is for

  • Hydraulic and process engineers
  • Maintenance engineers
  • Design engineers

What you get

  • New flow, head and power
  • Power saving

Interpreting the result

  • Plot the new pump curve against the system curve to find the real operating point.

References

  • Machinery’s Handbook, 29th edition (Industrial Press, 2012), printed pp. 3024–3027. Topic reference; no source tables or recommended settings are reproduced.

Learn the Concepts Behind This Tool

These BIZOMAT Library readings explain the method this tool uses, with worked examples.

BIZOMAT tools are screening and decision-support utilities. Verify important financial, engineering, safety, legal or operational decisions using appropriate professional standards and your organisation’s approved data.