Induction Motor Load Assessment (Current, Slip, Load, Energy)

From the nameplate and a measured speed, how heavily loaded is this induction motor, what current and torque is it running at, and what does it cost to run?

Assessment of a three-phase induction motor: rated line current, input power and torque from the nameplate (as the motor power tool), synchronous speed, slip and the load estimated from measured against rated slip (as the motor slip tool), the estimated output, torque and current at that load, the yearly energy and cost, and checks for overload and for an oversized (lightly loaded) motor.

Open the calculatorRuns in your browser. No account needed.

How this tool works

Inputs, units and where to find them

InputUnitTypical source
Line voltageVLine-to-line supply voltage.
Rated outputkWRated shaft output from the nameplate.
Rated power factorPower factor at rated load from the nameplate.
Rated efficiency%Efficiency at rated load from the nameplate.
Supply frequencyHzSupply frequency.
PoleschoiceNumber of poles (sets synchronous speed).
Rated speedrpmFull-load speed from the nameplate.
Measured speedrpmSpeed measured in service (tachometer or strobe).
Running hours per yearhHours the motor runs each year.
Electricity price$/kWhPrice of electricity.
Load below which the motor is oversized%Load share below which you treat the motor as oversized (your value).

What each input means

Open an input to see what it is, its units, the worked example and the common mistakes, with a small diagram.

What this means: Line voltage
Illustration: Line voltageA simple circuit with a supply and a load; Line voltage is one of its electrical quantities.~loadVExample: 415 VLine voltage
What it is
The line-to-line voltage of the three-phase supply to the motor, from the nameplate or a measurement at the terminals.
Units and format
Enter a number in V: volts. The form accepts 0.000001 V to 15000 V. Required: the tool does not calculate until every input is valid.
Example
The form opens with 415 V as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Rated current is inversely proportional to it.
Get it right
Use line-to-line, not line-to-neutral voltage.
What this means: Rated output
Illustration: Rated outputA motor driving a shaft; Rated output is the rate at which it does work, energy per second.PExample: 11 kWRated output
What it is
The rated mechanical output at the shaft, from the motor nameplate.
Units and format
Enter a number in kW: kilowatts. The form accepts 0.000001 kW to 100000 kW. Required: the tool does not calculate until every input is valid.
Example
The form opens with 11 kW as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Estimated output and energy cost scale with it.
Get it right
Rated output, not electrical input; convert hp to kW if needed (1 hp = 0.7457 kW).
What this means: Rated power factor
Illustration: Rated power factorTwo bars: a base value and the same value multiplied by Rated power factor, the factor.base valuewith factorcos φExample: 0.85Rated power factor
What it is
The power factor at rated load, from the motor nameplate or data sheet. It is used for the rated current.
Units and format
Enter a plain number with no unit. The form accepts 0.3 to 1. Required: the tool does not calculate until every input is valid.
Example
The form opens with 0.85 as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Get it right
Enter a decimal fraction, not a percentage.
What this means: Rated efficiency
Illustration: Rated efficiencyInput on the left and useful output on the right with the loss split off; Rated efficiency is output divided by input.inputuseful outputlossηExample: 91%Rated efficiency
What it is
The efficiency at rated load, from the motor nameplate or data sheet. The tool applies it at part load too, to estimate input power.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 40% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 91% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
A higher efficiency lowers estimated input power and energy cost.
Get it right
Type the percentage itself, for example 91, not 0.91.
What this means: Supply frequency
Illustration: Supply frequencyA repeating wave with one full cycle marked; Supply frequency counts cycles per unit of time.one cyclefExample: 50 HzSupply frequency
What it is
The frequency of the supply feeding the motor. With the number of poles it sets the synchronous speed.
Units and format
Enter a number in Hz: hertz (cycles per second). The form accepts 10 Hz to 400 Hz. Required: the tool does not calculate until every input is valid.
Example
The form opens with 50 Hz as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Get it right
If a variable speed drive feeds the motor, the slip method here does not apply directly.
What this means: Poles
Illustration: PolesThe options for Poles, with the one currently selected highlighted.2468+2 moreExample: 4Poles
What it is
The number of magnetic poles of the motor winding, which with the supply frequency fixes the synchronous speed.
Units and format
Choose one of 6 options from the list: 2; 4; 6; 8; 10; 12.
Example
The form opens with “4” selected as a worked example. Choose the option that matches your case.
Get it right
Work it out from the rated speed: on 50 Hz a motor near 1450 rpm is 4-pole.
What this means: Rated speed
Illustration: Rated speedA turning disc with a marker; Rated speed is how many full turns it makes in each minute.turns of the shaftper minuten_rExample: 1460 rpmRated speed
What it is
The full-load speed from the nameplate. Its slip from synchronous speed is taken as the slip at 100 % load.
Units and format
Enter a number in rpm: revolutions per minute. The form accepts 0.000001 rpm to 100000 rpm. Required: the tool does not calculate until every input is valid.
Example
The form opens with 1460 rpm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Get it right
Use the nameplate full-load speed, not the synchronous speed.
What this means: Measured speed
Illustration: Measured speedA turning disc with a marker; Measured speed is how many full turns it makes in each minute.turns of the shaftper minutenExample: 1475 rpmMeasured speed
What it is
The shaft speed measured with the motor running under its normal load, with a tachometer or strobe.
Units and format
Enter a number in rpm: revolutions per minute. The form accepts 0.000001 rpm to 100000 rpm. Required: the tool does not calculate until every input is valid.
Example
The form opens with 1475 rpm as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Estimated load is proportional to measured slip, so a lower speed means a higher load.
Get it right
A few rpm of reading error changes the estimate a lot; measure carefully.
What this means: Running hours per year
Illustration: Running hours per yearA timeline from a start mark to an end mark; Running hours per year is the time between them.startendtExample: 4000 hRunning hours per year
What it is
The number of hours the motor runs each year, from operating records or the shift pattern.
Units and format
Enter a number in h: hours. The form accepts 0.000001 h to 8784 h. Required: the tool does not calculate until every input is valid.
Example
The form opens with 4000 h as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
Effect on the result
Annual energy and cost rise in proportion.
What this means: Electricity price
Illustration: Electricity priceA price tag on one unit of measure; Electricity price is the cost for each unit (per hour, per kilogram and so on).$cost foreach unitExample: $0.25/kWhElectricity price
What it is
What you pay for one kilowatt-hour of electricity, from your power bill or contract.
Units and format
Enter a number in $/kWh: money per kilowatt-hour. The form accepts $0/kWh to $10/kWh. Required: the tool does not calculate until every input is valid.
Example
The form opens with $0.25/kWh as a worked example. It is an illustration, not a recommended value: replace it with your own figure.
What this means: Load below which the motor is oversized
Illustration: Load below which the motor is oversizedA bar of 100 parts with the share marked; Load below which the motor is oversized is that share out of 100. The bar follows the value you type.0 %100 %Example: 40%Load below which the motor is oversized
What it is
The load percentage below which you treat the motor as oversized for its duty, set by your own policy.
Units and format
Enter a number in %: percent: the number is read as a percentage, so type 8 for 8 %. The form accepts 0% to 100%. Required: the tool does not calculate until every input is valid.
Example
The form opens with 40% as a worked example. It is an illustration, not a recommended value: replace it with your own figure.

Method and formulas

  1. Rated current I = P ÷ (√3 V pf η); rated torque = 9549 P ÷ n (as the motor power tool).
  2. Synchronous speed n_s = 120 f ÷ poles; slip = (n_s − n) ÷ n_s; load ≈ measured slip ÷ rated slip (as the motor slip tool).
  3. Output ≈ load × rated output; input ≈ output ÷ η (rated efficiency assumed); torque = 9549 × output ÷ n.
  4. Current at part load estimated as load × rated current (an upper bound at light load, where the magnetising current dominates).
  5. Example: 1475 rpm means about 62.5% load: 6.875 kW and 44.509 N·m, costing 7,554.9 a year.

Limitations

  • The slip method is approximate (±20%), and voltage and temperature change the slip.
  • Efficiency and power factor fall at light load; measure input power for accuracy.
  • Example values are illustrations. Replace them with values for your actual task.

Typical uses

  • Check whether a motor is overloaded or oversized
  • Estimate running cost of a motor
  • Find torque at the operating point

Who it is for

  • Maintenance engineers
  • Energy managers
  • Electrical engineers

What you get

  • Rated current, input and torque
  • Slip and estimated load
  • Estimated output, current, torque and energy cost

Interpreting the result

  • A motor running under about 40% load wastes energy in poor power factor and efficiency: consider a smaller motor.

References

  • Machinery’s Handbook, 29th edition (Industrial Press, 2012), printed pp. 2569–2580. Topic reference; no source tables or recommended settings are reproduced.